Investigation on Partial Discharge of Power Cable Termination Defects using High Frequency Current Transformer
Main Article Content
Abstract
This paper presents partial discharge (PD) investigation of different cable termination defects. The medium voltage power cables as rated of 3.6/6(7.2) kV are applied. Finite Element Method Magnetic (FEMM) program is used as a simulation tool for electric field stress investigation. The partial discharges patterns are detected by using a commercial High Frequency Current Transformer (HFCT). The simple cases for internal, surface and corona discharge are firstly observed in order to investigate the performance of the HFCT. Then eight different case studies of cable termination defects are further investigated, which includes non-terminator, voids between XLPE and stress control, 20 mm. overlaps between semiconductor and stress control, particles on XLPE, non-smooth XLPE, needle tip on insulation screen, impropriate cable bending, and proper termination. The results are then compared with the results from a conventional PD diagnosis tool according to IEC 60270 standard. The results of PD detection show that the commercial product can detect the PD waveform and measure the electric charge when it is highly enough. The test can also identify trends toward breakdown and there severity due to improper cable termination defects.
Article Details
This journal provides immediate open access to its content on the principle that making research freely available to the public supports a greater global exchange of knowledge.
- Creative Commons Copyright License
The journal allows readers to download and share all published articles as long as they properly cite such articles; however, they cannot change them or use them commercially. This is classified as CC BY-NC-ND for the creative commons license.
- Retention of Copyright and Publishing Rights
The journal allows the authors of the published articles to hold copyrights and publishing rights without restrictions.
References
[2] R.-N. Wu, and C.-K. Chang, "The use of partial discharges as an online monitoring system for underground cable joints," IEEE Trans. Power Del., vol. 26, no. 3, pp. 1585-1591, Jul. 2011.
[3] X.J. Shen, and X.C. Jiang, "Development of online monitoring system for 1500 V ethylene propylene-rubber DC feeder cable of Shanghai urban rail transit generation," IET Transmission Distribution, vol. 5, no. 7, pp. 720-728, Jul. 2011.
[4] L. Yongfen, J. Shengchang, and L. Yanming, "Phased-Ultrasonic Receiving-planar array transducer for partial discharge location in transformer," IEEE Trans. Ultrason., Ferro electrics Frequency Control, vol. 53, no. 3, pp. 614-622, Mar. 2006.
[5] L.-J. Chen, T.-P. Tsao, and Y.-H. Lin, "New diagnosis approach to epoxy resin transformer partial discharge using acoustic technology," IEEE Trans. Power Del., vol. 20, no. 4, pp. 2501-2508, Oct. 2005.
[6] W. Xiaodong, L. Baoqing, Roman H.T., O. L. Russo, K. Chin, and K. R. Farmer, "Acousto Optical PD detection for transformers", IEEE Trans. Power Del., vol. 21, no. 3, pp. 1068-1073, Jul. 2006.
[7] S. Birlasekaran, and W. H. Leong, "Comparison of known PD signals with the developed and commercial HFCT sensors," IEEE Trans. Power Del., vol. 22, no. 3, pp. 1581-1590, Jul. 2007.
[8] A. Rodrigo, P. Llovera, V. Fuster, and A. Quijano, "Influence of high frequency current transformers bandwidth on charge evaluation in partial discharge measurements," IEEE Trans. Dielectrics Elect. Insulation, vol. 18, no. 5, pp. 1798-1802, Jun. 2011.
[9] F.P. Mohamed, W.H. Siew, J. J. Soraghan, S. M. Strachan, and J. Mcwilliam,"The use of power frequency current transformers as partial discharge sensors for underground cables," IEEE Trans. Dielectrics Elect. Insulation, vol. 20, no. 3, Oct. 2013.
[10] S. Birlasekaran, and W. H. Leong, "Comparison of known PD signals with the developed and commercial HFCT sensors," IEEE Trans. Power Del., vol. 22, no. 3, pp. 1581-1590, Jul. 2007.
[11] G.C. Montanari, A. Cavallini, and F. Puletti,"A new approach to partial discharge testing of HV cable systems," IEEE Elect. Insulation Mag., vol. 22, no. 1, pp. 14-23, Jan/Feb. 2006.
[12] A.J. Reid, M.D. Judd, R. A. Fouracre, B.G. Stewart, D. M. Hepburn,"Simultaneous measurement of partial discharges using IEC60270 and radio-frequency techniques," IEEE Trans. Dielectrics Elect. Insulation, vol. 18, no. 2, pp: 444-455, Apr. 2011.
[13] IEC Standard 60270, High Voltage Test Techniques-Partial Discharge Measurements, Ed. 3rd, 2000.