Multiple three-phase induction motors connected to a zigzag transformer
Main Article Content
Abstract
Many experiments have been conducted in this research work which is (i) connecting a zigzag transformer with an induction motor, (ii) connecting a zigzag transformer with multiple induction motors, and (iii) connecting multiple zigzag transformers with multiple induction motors. These experiments provide a thorough understanding of the sequence network connections under the single-phasing condition of a three-phase induction motor. Moreover, these experiments protect the three-phase induction motors from unbalancing voltage supply and allow the induction motor to start under unbalance voltage supply. Additionally, they keep the three-phase induction motor running even any one of the three phases disconnected from the power supply without creating excessive heat in the motor winding.