Investigation of the Effect of Harmonic Currents on Losses of Phase Shifting Transformers and Its Realization using a 15-Degree Phase shifting Transformer
Main Article Content
Abstract
The trend of energy savings has been widely interested and phase shift transformers (HMT) have been extensively used. This paper presents the investigation of the effect of harmonic currents on losses of the HMT. In this paper, a 15-degree HMT with quad secondary winding is applied to find the relationship between harmonic currents and losses of the HMT. This relation can be met by testing the active power of primary and secondary sides while the HMT supplies for two and four non-linear loads at 25%, 50%, 75%, and 100% rated currents, respectively. The results reveal that harmonic currents affect winding eddy current losses significantly and the losses for loading the two secondaries 1 and 2 are the same as loading the two secondaries 1 and 3 while both %THDi are different. However, for loading the secondaries 1 and 2, the %THDi is more than 15% so it is not met IEEE 519 Std. while the HMT is supplied with four loads, the %THDi has met IEEE 519 Std. and the losses are less than 57% compared to one load. As a result of these, if the HMT is applied to an adjustable speed drive system, it is not only reduced the harmonics but also saved the energies.
Article Details
This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
ลิขสิทธ์ ของมหาวิทยาลัยเทคโนโลยีราชมงคลพระนครReferences
B. K. Bose, Modern Power Electronics and AC Drives, Pearson Education, New Delhi, 2001.
IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE std. 519-1992, 1992.
Limits of Harmonics in Electricity for Business and Industry, PRC-PQG-01-1998, 1998.
E.F.Fuchs, D.Yildirim and W.M.Grady, “Measurement of eddy-current loss coefficient PEC-R, derating of single-phase transformers, and comparison with K-factor approach,” IEEE Trans. Power Delivery, vol. 15, pp. 148–154, Jan. 2000.
T.C. Sekar, B.J. Rabi, “A Review and Study of Harmonic Mitigation Techniques,” in Proc. of ICETEEEM-2012, IEEE, 2012, pp. 93-97.
B. Singh, S. Gairola, B. N. Singh, A. Chandra, and K. Al-Haddad, “Multipulse AC–DC converters for improving power quality: A review,” IEEE Trans. Power Electron., vol. 23, no. 3, pp. 260–281, Jan. 2008.
J. Rodriguez, J.-S. Lai, and F. Z. Peng, “Multilevel inverters: A survey of topologies, controls, and applications,” IEEE Trans. Ind. Electron., vol. 49, no. 4, pp. 724–738, Aug. 2002.
B. Singh, G. Bhuvaneswari, and V. Garg, “A novel polygon based 18-pulse AC–DC converter for vector controlled induction motor drives,” IEEE Trans. Power Electron., vol. 22, no. 2, pp. 488–497, Feb. 2007.
B. S. Lee, P. N. Enjeti, and I. J. Pitel, “A new 24-pulse diode rectifier system for ac motor drives provides clean power utility interface with low kVA components,” in Proc. IEEE IAS’96, 1996, pp. 1024–1031.
S. Choi, B. S. Lee, and P. N. Enjeti, “New 24-pulse diode rectifier systems for utility interface of high power AC motor drives,” IEEE Trans. Ind. Appl., vol. 33, no. 2, pp. 531–541, Mar./Apr. 1997.
F. J. Chivite-Zabalza, A. J. Forsyth, and D. R. Trainer, “A simple passive 24-pulse ac–dc converter with inherent load balancing,” IEEE Trans. Power Electron., vol. 21, no. 2, pp. 430–439, Mar. 2006.
B. Singh, G. Bhuvaneswari, and V. Garg, “T-connected autotransformer-based 24-pulse ac–dc converter for variable frequency induction motor drives,” IEEE Trans. Energy Conv., vol. 21, no. 3, pp. 663–672, Sep. 2006.
B. Singh, G. Bhuvaneswari, and V. Garg, “24-pulse ac–dc converter for power quality improvement in vector controlled induction B motor drives,” Int. J. Elect. Power Compon. Syst., vol. 34, no. 10, Oct. 2006, pp. 1077–1098.
B. Singh, V. Garg, and G. Bhuvaneswari, “Polygon connected autotransformer based 24-pulse ac–dc converter for power quality improvement,” in Proc. India Int. Conf. Power Electron. IICPE’06, Chennai, India, Dec. 19–21, 2006, pp. 125–130.
B. Singh and S. Gairola, “A fork connected auto-transformer based 24-pulse ac–dc converter,” in Proc. India Int. Conf. Power Electron. IICPE, Chennai, India, Dec. 19–21, 2006, pp. 183–187.
B. Singh, V. Garg, and G. Bhuvaneswari, “Polygon-connected autotransformer-based 24-pulse AC–DC converter for vector controlled induction-motor drives,” IEEE Trans. Ind. Electron., vol. 55, no. 1, pp. 197–208, Jan. 2008.
P. Kiatsookkanatorn, N. Watjanatepin, “Power Quality Improvement by Using a 15-Degree Phase Shifting Transformer for 24-Pulse Rectifiers,” LADKRABANG ENGINEERING JOURNAL., vol 34, no 1, PP 9-16, March. 2017.
B. Wu, High-Power Converters and AC Drives. Piscataway, NJ: IEEE Press, 2006, pp. 68-76.
D.Yildirim and E.F Fuchs, “Measured transformer derating and comparison with harmonic loss factor (FHL) approach,” IEEE Trans. Power Delivery, vol. 15, pp. 186 – 191, Jan. 2000.
A. Elmoudi, M. Lehtonen and H. Nordman, “Effect of harmonics on transfonners loss of life,” in IEEE Int 'I Sympos. Elec. Insulation, 2006, pp. 408-411.
N. Mohan, T. Undeland and W.P. Bobbins, Power Electronics - Converters, Applications and Design, John Wiley & Sons, 3rd Edition, 2003. pp.103 – 106.
L. W. Pierce, “Transformer design and application considerations for nonsinusoidal load currents,” IEEE Trans. on Ind. Appl., vol. 32, no. 3, pp. 633–645, May/June 1996.
MIRUS international Inc. (2021, September 27). Harmonic Mitigating Transformers. [Online]. Available: http://www.mirusinter- national. com.
IEEE Recommended Practice for Establishing Liquid-Filled and Dry- Type Power and Distribution Transformer Capability when Supplying Nonsinusoidal Load Currents, IEEE C57.110-2008, August 2008.
B.L.Theraja, A.K. Theraja, “Transformers,” in A Text Book of Electrical Technology S.I units, vol. 2: AC and DC machines, 23rd ed. India, S Chand & Co Ltd., 2006, pp. 1169.